ENERGY MANAGEMENT AT CITY OF PORI THE CITY OF THE PORI Technical Services Centre Building Manager Unit Jouni Lehtinen Project Engineer Phone: +358 44 7011680 Email: jouni.lehtinen@pori.fi
THE CITY OF PORI Founded in 1558 Located on the southwest coast of Finland 140.000 people live in the Pori region The Pori area is the most industrialised regions in Finland Deepwater drilling and production platform The world's second largest fabricator of copper products
TECHNICAL SERVICES CENTER Building Management Unit The unit takes care of buildings owned by the city and helps central administration and other administrations in tasks concerning construction. The unit also takes care of construction and maintenance of city buildings Health Centre and Hospital Buildings Basic School and College Buildins Adminstration Buildings Day-care Buildings Sport Buildings
ENERGY AND ENVIROMENTAL MANAGEMENT The environmental and development conference of the UN (UNCED) suggested in Rio de Janeiro in 1992 that all municipalities in the world should prepare a local action programme of sustainable development, Agenda 21. In the region of Pori the work started in the beginning of 1993 (Energy audits). In 2000 estabilished The Programme of the Energy Management with Ministry of trade and Industry. In 2001 organizations form a dedicated Energy Management Team and institute an energy policy
THE ENERGY MANAGEMENT TEAM Representative from each administrative sectors that significantly affects energy use: Task: Technical Services Centre Pori Energy The Water Works of Pori Port of Pori Strategy Data Collection and Management Collect energy use information and document data over time Energy audits Action Plan Educate (Users organization) Motivate (Offer cash bonuses)
Guidelines for Energy Management Make Commitment District heat will be supported Increasing the use of renewable energy sources Assess Performance & Set Goals Saving energy and improving efficiency Adapting international agreements to local level Energy aspects in the procurement of goods Re-Asses Recognize Achievements Create Action Plan Evaluate Progress Implement Action Plan
Problems Attitudes Resources
Energy usage information and documented data Heating Water Electricity 139 Buildings ^ 1.592.400 rm3 Heating: 122.200 /annual - 5,0 % CO tn 22.200 /annual
SUMMARY Good Energy Management is Good Business has saved over 350.000 /annual through effective energy management
THANK YOU!!!
Pääkohdat Porin kaupungin teknisistä energiansäästötoimenpiteistä Keypoints in energy management at city of Pori (technical wiew) Systeeminsuunnittelija Kari-Matti Haapala Porin kaupungin Tekninen palvelukeskus Systems designer Kari-Matti Haapala Technical Services Centre of the city of Pori
RAKENNUSAUTOMAATIO BUILDING AUTOMATION Olosuhteiden reaaliaikainen tarkkailu rakennusautomaatiojärjestelmien avulla avainkiinteistöissä Real time indor climate monitoring at major buildings with building automation systems Keskusvalvomon rakenusautomaatiojärjestelmiin liitetty yli 50 avainkiinteistöä There is over 50 major buildings conected in the building automation central
RAKENNUSAUTOMAATIO BUILDING AUTOMATION Laitteistojen käyntiajat ja lämpötila asetukset tarkistetaan puolivuosittain Ensimmäinen tarkastuskierros (2001) toi yli 16.000,00 laskennalliset säästöt Time schedules of the systems and tempperature setpoints are been recalculated every six months First recalculation round (2001) brought over 16.000,00 calculated savings Tarkka vastaanottomenettely rakennusautomaatiojärjestelmissä Anturikalibroinnit, pistekohtainen tarkistus Strict acceptance inspection in building automation systems delivery. Sensor calibration, point to point inspection
ENERGIANKULUTUKSEN SEURANTA MONITORING OF ENERGY CONSUMPTION Mittareiden luennan vastuuhenkilöt määritelty ja työ ohjeistettu The collecting of the energy meter readings is personified and the work is strictly instructed Luenta sähköiseen lukulaitteeseen Luentavirheiden vähentyminen, Nopea reagointi kulutuspoikkeamiin Colecting of the energy meter readings is made by scanner Reduce of the meter reading errors, Fast reacting in the consumption differences
ENERGIANKULUTUKSEN SEURANTA MONITORING OF ENERGY CONSUMPTION Kiinteistöjä kulutusseurannassa 161 kpl Buildings in the consumption monitoring system 161 Kaukolämpömittauksia 114 District heating meters 114 Sähkömittauksia 241 Electrical energy meters 241 Vesimittauksia 175 Water meters 175 Polltoöljy 31 Domestic heating oil meters 31
YHTEENVETO SUMMARY Tekniset keinot energiansäästämiseksi ovat erittäin käyttökelpoisia ja välttämättömiä, mutta ne tuottavat tulosta vain osaavissa ja motivoituneissa käsissä. Tecnical means to reduce energy consumption are very usefull, and necessary, but they bring out results only in motivated and competent hands.
Kiitos Aitäh Thank you
Case: Päiväkoti Untuva Maalämpö Environment friendly heating
LÄHTÖTIEDOT Päiväkoti untuva 413 hum2, 2000m3 Rakennettu 1890 yksityisasunnoksi Peruskorjattu päiväkodiksi 1985 Öljylämmitys Talvella 2004 todettiin lukuisten huoltojen jälkeen öljypoltin epäluotettavaksi ja kattila vaihtokelpoiseksi Kaukolämpöä ei saatavissa alueelle
HANKESUUNNITTELU Suunnittelu käynnistettiin alkuvuodesta 2005 Suunnittelutoimiston suunittelu viittellistä, tarkesuunnittelu laitetoimittajalta Vanha öljykattila ja poltin jäivät reserviksi huippupakkasten (Yli -16 C) ajaksi Kustannusarvio 32 000 alv0% Laitetoimittajan valinnan jälkeen aloitettiin asennustyöt heinäkuussa 2005 Laitetoimittajaehdokkaiden esittämät takaisinmaksuajat vaihtelivat huomattavasti. Tarjoushinta vastasi kustannusarviota
Poraus Technical Services Centre Peruskallio 30 m (lähtötieto 5 m) => Kustannusten kasvu
Laitteistoasennus Asennustyöt kohteessa kestivät kaksi viikkoa
TULOKSET Vuoden 2006 kulutuseurannan mukaan kiinteistön lämmitysenergian kulutus on pudonnut 71% Sähköenergian kulutus noussut 12%
ONGELMAT Lähtötietojen puutteellisuus Maaperätutkimus paikan päällä suotavaa Käyttöönoton ongelmat Järjestelmän kehno ilmaus aiheutti aluksi ongelmia
Kiitos